Alarm code: 1007

M3 - Rotary heat exchanger motor stuck

Description

The system indicates that the rotary heat exchanger is running too heavy or is completely stuck. As a safety measure, the rotor motor is stopped pending check/reset of the alarm.

Instructions

  1. Try to reset the alarm following the procedure described for the Flexit GO app or control panel, dependant on which device you are using. 
  2. Switch off the supply voltage to the unit by pulling out the mains plug. Look for a possible reason why the rotor runs heavy/gets stuck. If ice formation is the cause, the module must be removed (see user manual) to allow the ice to melt. Also remove any moisture/ice that remains in the unit. In case of recurring problems with de-icing, the commissioned air flows should be reviewed to ensure correct operation. Consider enabling the defrost function. 
  3. In case this action doesn’t solve your problem, please contact your service partner.